Maintenance
To ensure the performance of battery, the
battery should be correctly inspected and maintained. The maintenance methods
are recommended as follows.
Monthly Maintenance
■ Keep the
battery space clean.
■ Measure and
record the ambient temperature of the battery-room and battery container
temperature.
■ Check
battery cleanliness, terminal damage and heating track, container and lid
damage
and over heating track.
■ Check battery
and battery rack connection, spring mat and bolts connected tight or not,
input terminal heating or not, connected
terminal between layer heating or not.
■ Check the
container sealing, leakage/potential leakage or not in terminal, valve and
container position.
■ Check charge
temperature compensation function in normal or not, parameters setting
correct or not, equalizing charge voltage,
floating charge voltage period and other parameters reasonable setting or not.
■ Measure and
record the total voltage and floating current of the battery system.
Quarterly Maintenance
■ Repeat every
item of monthly inspection.
■Measure and
record the floating voltage of each on-line battery. After temperature
emendation, if more two batteries with a
voltage of lower than 2.18V, the battery system needs equalizing charge. If the
problem is not solved, go on annually maintenance even three yearly maintenance
items. All the above methods fail, please contact our after-sale service
center.
Annually Maintenance
■ Repeat every
item of quarterly maintenance and inspection.
■ Check
whether the battery beyond service expiry or not.
■ Perform a
discharge test to check the exact load every year, discharge 30%-40% of the
rated capacity.
Maintenance notes
■ Please use
insulated tools when operation and maintenance, any metal objects to be put on
top of the battery shall be strictly prohibited;
■ Please do
not use any organic solvent to clean batteries;
■ Please do
not take down safety valve or add any substance into battery;
■ Please do
not smoke or set out fire near batteries;
■ Please keep
battery fully charged within 24 hours after discharge, avoid capacity affected;
Check whether safety valve twisted tightly or not, but please do not take
down it;
■ Stored
battery performance could be in degeneration, please put the battery in
operation
early;
■ Only
professionals shall be allowed to maintain the battery.
|